CONTACT

Call: +971 5 448 448 58
Fax: +971 4 355 8090
E-mailThis email address is being protected from spambots. You need JavaScript enabled to view it.

Call: +971 5 448 448 58
Fax: +971 4 355 8090
E-mailThis email address is being protected from spambots. You need JavaScript enabled to view it.

Fibershield-H Sprinkler protection

Fibershield-H Sprinkler protection



The horizontal textile fire protection closure to seal openings in ceilings

Special design: Modification of the linear closing direction



Protection targets



Insulation with sprinkler 
protection in case of fire
Sprinklerschutz
Classification

El 120

Fabric

Protex 1100.1 A2
special coating

Test reports

UB III/08-016





Description of the Fibershield-H system

  • Big ceiling openings for width of up to 20 m and high drop lengths (s. table)
    (horizontal fire-resistant glazings can only be used for approx. 2 m x 2 m)
  • Highest variability for the construction and the design
  • Safe closing process by the “Duplex” system, optional with a control unit for a guaranteed power supply
  • Tensioning ropes in a distance of 1,5 m to support the fabric with large dimensions as well as to withstand the pressure load in case of fire
  • Flexible installation (under the ceiling, in the embrasure)
  • Less space requirement



 Table of dimensions (standard design)

System version CW CL a
(mm)
b
(mm)
t
(mm)
h
(mm)
f
(mm)
Gas spring < 1,4 m ≤ 1,5 m 120 109 190 200 190
Gas spring
< 1,4 m
≤ 4,5 m 150 109 235 290 235
Gas spring
< 4,5 m ≤ 2,9 m 120 109 190 250 190
Gas spring < 4,5 m
≥ 2,9 m - < 5 m 
150 109 235 290 190
Gas spring ≥ 4,5 m < 2,9 m
120 225 190 250 190
Gas spring ≥ 4,5 m - < 30 m
≥ 2,9 m - < 5 m
150 225 235 320 235
Duplex < 20 m ≥ 2,9 m - < 8,5 m
160 355 274 355 80

 

 



 
Clear width (CW)   Drop down length (CL)



Range of casings


 
Fixed bearing   Floating bearing



Bottom bar + Feeding edge





Side guide





Alternatives for the installation


Installation underneath the ceiling Installation into the opening in the ceiling

Control units for fire protection closures

Control units for single closures:

Control units for multiple closures: