Protection targets

Protection targets



 

Charateristics according to DIN EN 13501-2

Definition/ 
classifikation
Achieved protection targets withhin the fire resistance classes
Approvals
(tests acccording to DIN EN 1363- 1 and DIN EN 1364-1
and DIN EN 14600 durability and functional test)

E

Integrity

is the resistance against fire to avoid a passage of flames or hot gases. 
(The protection target EI is achieved by fire load free zone EI 30 = 1,0 m, EI 60 = 1,5 m, EI 90 = 2,0 m.)
Protection target EI 30: x = 1000 mm
Protection target EI 90: x = 2000 mm

E 90

E 120

E 240 

UB III/B-06-005
UB III/B-07-010-1
UB III/B-05-020
UB III/B-06-016
GU IV/97-73
UU IV/97-25
UB III/B-04-045
LP-1216.2/02
UB III/B-08-033
3344/097/09
UB 3.1 / 09-018
UB 3.1 / 09-021
UB 3.3 / 09-020
IBS 08062416
UB 3.3 / 10-018-1
UL 10D for E120
UL 10P for E120
UL 10C for E120

EW

Integrity with a limitation of heat transmission

Limitation of the heat transmission is the characteristic to reduce heat transferred through a fire protection system to limiting materials. 
(The protection target EI is
achieved by fire load free zone).
Protection target EI 30: x = 200 mm
Protection target EI 60: x = 300 mm
Protection target EI 90: x = 500 mm

EW 30

EW 60

EW 90

EW  120 

UB III/B-08-012
UB III/B-07-003
UB 3.3/ 10-035-1
UB 3.3/ 11-009-1

E+

Sprinkler

Insulation with intensified sprinkler protection

Insulation is the ability of the system to avoid the transmission of fire caused by heat transmission. The transmission has to be limited in a way, that neither the opposite fire side surface nor any materials near to this surface may ignite an so persons are protected. 

x = 200 - 500 mm depending on the environment

EI 90

EI 120

EI 180 

UB III/B-08-016
UB III/B-05-006
IBS 08062415
UB III/B-07-10-2

E+

Water film

In case of fire - heat insulation with a water film
(The surface temperature is lower than the admissible limit value)

 EI 90

EI 120

EI 180

08/32309876

Part 1
2011-Efectis-R0495

EI

dry

Insulation without water in case of fire

 EI30

EI 60

(3162/794/10)-AH
(3699/959/10)-AH
304/878/09
3053/504/10

Transmission from one floor to another

Avoidance of transmission of flames from one level to another without (with) balustrade

The necessary barrier (or lintel) of 1 m height is automatically created in case of fire. 

B 15045
UB III/B-05-006-A1
proof of weathering

Extinguishing


Creation of sections

Limitation of a room which is usually not there to avoid the transmission of flames or hot gases to the room without fire. Enclosure by textile fire
protection closures with the targets: limitation of the fire, smothering of the fire, extinguishing of the fire by gases or water-spray.

 

Enclosure by textile fire protection closures with the target to: 

  • limit the fire
  • quench the fire
  • extinguish the fire with gases or water-spray