Smokeshield-S, class D=600°C

Smokeshield-S


The automatic smoke curtain which creates sections and matches highest demands
class D=600°C

 


 CE - Nr. 0761 - CPD 0191 Fire performance of complete smoke curtain
Approval applied
  • Rectangular oder polygon shaped base area of the smoke curtain
  • Outer dimensions up to 16m and drop lengths of up to 6 m
  • Designed for a high time classification and temperature load D=600°C
  • No remaining openings - neither in the upper area nor at the corners
  • Pillars are not necessary, although complete tightness even in case of the high pressure
  • Small height of the casing - approx. 150 mm
  • Standard drive system "Gravigen", that is closing without auxiliary energy, no fire resistant cables are necessary
  • Redundant drive system as crash protection
  • Suitable (approved) as smoke curtain that is flush with the floor

 



Dimensions




 
 

Circumference 
of the system

Drop length
(mm)

h
(mm)

< 50 m
≤ 3 m 490 125
< 50 m
> 3 m - < 6 m 490 225

At least 2 drive units and one additional drive unit for each 10 m over 20 m circumference
 


Range of different runs of the smoke curtain


 



Range of casings


Standard   Optional with safety device<br/>   (Infrared)  
Standard   Optional with safety device
(Infrared)
 

1 = Smoke protection fabric

   


Closing tray


Standard Optional with spots or light strip (possibly raise of construction height)




CE-classification




Patented tubular motor 
with Gravity Fail Safe technology





Protex 600.1 A2 / 1100.1 A2 

 
Labelling
EN 12101-1
Stöbich
Smokeshield-S system
Automatic smoke curtain Typ ASB 1 / ASB 3
closing without electric power
Temperature classification D120
(600°C / 120 min)
Closing speed
(depends on the drive)

from 0,15 m/sec. uo to approx 0,30 s/m
e.g. drop length 9m = within 60s in the closed position

Gap-casing (a-f) 0 mm
Gap-edges (g) embrasure 0 mm
Gap-joint (h) 0 mm
Max. permeability of the
smoke curtain fabric
(max. 25m3/m2/h)
< 1m3/m2/h
test temperature at ambient temperature and at 200°C
Free area-casing = length of the casing x gap casing = Lx0=0 mm2
Free area-edges = D x gap edges
Free area-joints = D x gap joint x number of joints

EG conformity certificate
DIN EN 12101-1

0761-CPD-0191
General approval from the
Building Authority for the fabric
Z - 56. 429 - 916

D=Drop length of the smoke curtain

 