Supercoil without side guides, Class D=600°C

The traditional automatic smoke curtain to match highest demands and large dimensions
without side guides, class D=600°C


CE - Nr. 0761 - CPD 0060
Characteristics of the complete smoke curtain during a fire are corresponding to the approval no. Z - 56.412 - 935

  • Made of one piece up to 50m width and 9,5m drop
  • For highest time classifications in case of fire load D = up to 600°C
  • No remaining openings within the casing area
  • Only 1 drive unit is necessary, therefore reduced compexity for the installation
  • Highest variability concerning engineering and design
  • Standard drive system “Gravigen”, that is closing without auxiliary energy, no fire resistant cables are necessary
  • High number of cycles of the motor = 10.000
  • The system weight is 20-30 kg per mtr. (system width)
  • Suitable (approved) as smoke curtain that is flush with the floor
  • Combination Stripecoil with technology of Supercoil for person passage in restricted areas


Variation with an emergency door

       
Optional with integrated emergency 
door for floor closing smoke curtains
       Combination Supercoil/Stripecoil


Dimensions


   
   

a = side guide
b = gap without side guide

System table (without side guides)

 

Fabrice Width of the System Drop lenght
(mm)
h
(mm)
Protex 600.1 A2 / 1100.1 A2 > 0,9 m - ≤ 1,4 m ≤ 3,5 m 190 250
Protex 600.1 A2 / 1100.1 A2 > 1,4 m - ≤ 50 m ≤ 3,5 m 190 200
Protex 600.1 A2 / 1100.1 A2 ≤ 50 m > 3,5 m - ≤ 6 m 190 250
Protex 600.1 A2 / 1100.1 A2 ≤ 50 m > 6 m - ≤ 9 m 235 290

 

 



Range of casings


     
Standard fixed bearing   Standard floating bearing   Range of special constructions   Range of special constructions



Bottom bars


Standard for small widths
4,6 type   Heavy type   9,6   Narrow type 5,61
4,6 type   Heavy type 9,6   Narrow type 5,61

Standard for large widths
3,84 type  Self-levelling bottom<br/>  bar without safety edge   3,84 FK type  Self-levelling, optional with safety edge   Self-levelling bottom bar without<br/>   safety edge, under the ceiling
3,84 type Self-levelling bottom
bar without safety edge
  3,84 FK type Self-levelling, optional with safety edge   Self-levelling bottom bar without
safety edge, under the ceiling



CE- system classifications




Patented tubular motor with Gravity Fail Safe technology





Protex 600.1 A2 / 1100.1 A2 

 
Labelling
EN 12101-1
Stöbich
Supercoil
 system
Automatic smoke curtain Typ ASB 1 / ASB 3
closing without electric power
Temperature classification D60
(600°C / 60 min)
Closing speed
(depends on the drive)
from0,15 m/s to 0,30 m/s
e.g. drop length 9m = within 60s in the closed postion
Gap-casing (a-f) 0 mm
Gap-edges (g) embrasure

g = 15 mm + 30 mm for fixed bearing without side guide
g = 30 mm + 30 mm for floating bearing without side guide

Gap-joint (h) 0 mm (standard ceiling installation)
Max. permeability of the smoke curtain fabric
at ambient temperature and at 200°C
(max. 25m3/m2/h)
< 1m3/m2/h
Frea area-casing = length of the casing x gap casing = Lx0=0 mm2
Frea area-edges = D x gap edges
Frea area-joints = D x gap joint x number of joints
EC conformity certificate 0761 - CPD - 0060
General approval from the Building Authority for the fabric Z - 56. 429 - 916 / Z - 56.412 - 935
D=Drop length of the smoke curtain

Control units for smoke curtains

Control units for single smoke curtains:

Control units for multiple smoke curtains: